Starting from LOCUS 2.18.6, you can configure an event (alarm) that is raised when a device reports a parameter value that crosses a threshold you define. For example, you can get an event when the temperature reported by a sensor drops to 0 °C or lower, or when the humidity rises above 80 %.
This is done with the Threshold Breach event trigger, available in the Device Health & Monitoring category of the Add Event Rule wizard.
Typical use cases:
- Cold-chain and freezer monitoring (e.g., Temperature ≤ 0 °C).
- Overheating detection (e.g., Temperature ≥ 30 °C).
- Humidity or other environmental limits (e.g., Humidity > 80 %).
- Device-state alarms for discrete parameters (e.g., door/window open, impact alarm).
Supported devices: TEKTELIC sensors, trackers and beacons. The list of parameters available for a threshold depends on the selected device model. The Threshold Breach trigger is displayed only if at least one device model that supports it is added to your account.
- Go to Event Rules → Add Event Rule.
- Step 1: Enter a name (e.g., “Freezer temperature low”), select the site, and click Next.
- Step 2: Select Threshold Breach and click Next.
- Step 3: Select Specific devices and choose your sensor(s). Set Parameter = Temperature, Operator = Less than or equal to (≤), Threshold Value = 0. Click Next.
- Step 4: Optionally enable a webhook, then click Save.
From now on, an event appears in Events every time one of the selected sensors reports 0 °C or less. Detailed description of every step is given below.
- A rule monitors the selected parameter of the devices in its Device Scope.
- Each time a device reports this parameter, LOCUS compares the reported value with the configured condition (Parameter – Operator – Threshold Value).
- Event opened: when the reported value satisfies the condition, an event is created with Activity = Open.
- Event closed: when the reported value no longer satisfies the condition (the inverse condition is met), the event Activity changes to Closed. The event is kept for history.
- A new event for the same device and rule is created only after the previous event is closed.
- If webhook notifications are enabled for the rule, a notification is sent to your external system when the event is triggered.
Example: a rule with condition Temperature ≤ 0 °C opens an event when a sensor reports -1.5 °C. The event stays Open while the sensor keeps reporting values ≤ 0 °C and becomes Closed once the sensor reports a temperature above 0 °C.
Conditions: You need admin permissions or explicit rights to add event rules, and read access to the devices you want to monitor.
Steps:
-
Go to Event Rules and click Add Event Rule.
-
Step 1: Add Rule Details
- Event Rule Name: Input the name of the rule (e.g., “Freezer temperature low”).
- Site: Select the site. Only devices of this site will be available for selection in Step 3.
- Description: Input an optional description.
- State: Check the box to enable the rule upon saving (default: enabled).
- Click Next to proceed or Cancel to discard.
-
Step 2: Select Event Trigger
- Event triggers are grouped by category (Location, Device Health & Monitoring). Only triggers supported by device models in your account are displayed.
- Under Device Health & Monitoring, select Threshold Breach – Triggers when a monitored device reports a parameter value that matches the configured threshold condition.
- Only one event trigger can be selected per rule.
- Click Next to proceed or Cancel to discard.

-
Step 3: Define Event Criteria
Device scope
-
Device: Choose which devices are monitored:
-
All devices – all supported devices of the selected site.
-
Specific devices – only the selected devices. When this option is selected, the following fields are available:
- Filter by Tags: Narrow the device list by tags assigned to devices.
- Filter by Device Model: Narrow the device list by device model (e.g., VIVID).
- Select devices: Select one or more devices (e.g., VIVID_V2-0239AE). Required.
-
Threshold Conditions
- Parameter: Select the parameter to monitor (e.g., Temperature). The list contains only the parameters supported by the selected device models.
- Operator: Select the comparison operator (e.g., Less than or equal to (≤)).
- Threshold Value: Input the threshold value. The unit of the parameter is displayed next to the field (e.g., °C). For discrete parameters (e.g., door state, alarm status), specify the state that should trigger the event.
- Fields marked with an asterisk (*) are required.
- Click Next to proceed or Cancel to discard.
The fields of this step are the same when you add and when you edit a rule – see the screenshot in Edit a Threshold Breach Event Rule.
-
-
Step 4: Set Notification Preferences
- Optionally enable webhook notifications and set the URL, Headers and Body, as for other event rules. See Event Rules and Webhook configuration.
- Click Test Webhook to verify the connection.
- Click Save to create the rule; Cancel to discard.
- Expectations: The new rule appears in the Event Rules list with Event Trigger = Threshold Breach. If the rule is enabled, LOCUS starts evaluating new reports from the devices in scope. The Triggered counter starts at “0”.
Conditions: You need admin permissions or explicit rights to edit event rules.
Steps:
-
In the Event Rules list, click More Actions (…) next to the rule and select Edit.
-
Step 1: Edit Rule Details – update the name, site, description or state.
-
Step 2: Review Event Trigger – the event trigger is displayed for review only. The trigger of an existing rule cannot be changed. To use another trigger, create a new rule.
-
Step 3: Review Event Criteria – update the device scope (all/specific devices, tags, device model, devices) and the threshold conditions (parameter, operator, threshold value).

Example: the rule monitors the Temperature of the VIVID_V2-0239AE sensor and triggers an event when it is less than or equal to 20 °C.
-
Step 4: Edit Notification Preferences – update the webhook settings if needed.
-
Click Save to confirm changes; Cancel to discard.
- Expectations: The updated conditions are applied to new device reports. Events created before the change are not modified.
Deleting a Threshold Breach rule works the same way as for any other event rule – see Event Rules.
Threshold Breach events are displayed in:
- Events menu (main table).
- Home and Floor Plans → Events tab, with an event marker on the map.
- Sensors / Devices / Beacons → device details → Events tab.
Each event shows:
- Triggered At – date and time the event was created.
- Activity – Open (the condition is currently true) or Closed (the condition is no longer true; the event is kept for history).
- Event Status – Unacknowledged / Acknowledged. By default, only unacknowledged events are displayed.
- Trigger Name and Event Rule Name.
- Event details – the reported value (e.g., Temperature -1.5 °C), the configured threshold condition (e.g., Temperature ≤ 0 °C), device/sensor name and Device EUI.
Events can be acknowledged and exported to .CSV from the Events list and Events tabs.
Thresholds configured in Threshold Breach rules are also visualized in the sensor screens:
-
Sensors list (main table): parameter values that triggered a Threshold Breach event are highlighted.
-
Sensor History – top cards: each parameter card shows the configured threshold(s) as
(e.g., ≤ 0 °C). Values that triggered an event are highlighted. -
Sensor History – chart:
- For numeric parameters, thresholds are displayed as horizontal reference lines labeled
(e.g., Temperature ≥ 30 °C). - For discrete parameters, the threshold state is highlighted on the Y-axis.
- Values that triggered an event are highlighted on the chart.
- Threshold lines are visible by default. To hide them, click the Settings (gear) icon of the chart and turn off Thresholds in Visibility Preferences. The option is disabled when none of the selected parameters have configured thresholds. See Analyzing Sensor Measurements.
- For numeric parameters, thresholds are displayed as horizontal reference lines labeled
-
Sensor History – table view: values that triggered an event are highlighted.
See also Sensors Overview, Sensor Events and Sensor History overview.